48v inverter output short circuit and output voltage protection instructions

Column:Industry News Time:2021-10-19
When the inverter output feedback does not have a zero-crossing point for 64ms continuously,

(1) Output short-circuit protection of the inverter

When the inverter output feedback does not have a zero-crossing point for 64ms continuously, it is regarded as an output short circuit, the UPS output is turned off, the UPS beeps for a long time and an alarm is displayed on the panel.

(2) Output voltage protection of the inverter

When the inverter output feedback voltage is lower than 140V or higher than 276V for 80ms continuously, it is regarded as output undervoltage or overvoltage for protection, the UPS transfers to bypass mode, the UPS beeps for a long time and an alarm is displayed on the panel.

(3) BUS overvoltage protection of the inverter

When the BUS voltage exceeds 440V for 64ms continuously, it is considered that the BUS is over-voltage and protected, the UPS transfers to the bypass mode, the UPS beeps for a long time and an alarm is displayed on the panel.

(4) Inverter current limiting protection

The protection circuit monitors the output current value. If it exceeds 3.6 times the rated current, the current-limiting protection circuit immediately turns off the PWM and resets the PWM at a 19.2kHz cycle until the output current value is less than 3.6 times the rated current.

(5) Over-temperature protection of the inverter

When the system temperature is too high, the temperature switch trips, making the UPS transfer to bypass mode, the UPS beeps for a long time and an alarm is displayed on the panel (detection time 0.5s).

(6) Load protection of inverter


110%~130%

If the UPS detects that the load exceeds 110% before jumping from the bypass to the inverter, it cannot enter the inverter state. At this time, the UPS beeps once every 0.5s and displays the status on the panel. If the load is detected between 110% and 130% after power-on, the UPS will beep once every 0.5s and display the status on the panel. After 10s, the UPS will switch to bypass mode; after that, if the load is reduced to below 100%, the UPS Restart the soft boot. If the UPS detects that the load is between 110% and 130% in the battery power supply mode, the UPS will beep every 0.5s and display the status on the panel; if the load is not reduced below 100%, the UPS will transfer to bypass after 10s Mode, this state can only be released by pressing the OFF button.


Greater than 130%

If the load is detected to be greater than 130% after power-on, the UPS will beep once every 0.5s, and the status will be displayed on the panel, and the UPS will transfer to the bypass state. After that, if the load is reduced to below 100%, the UPS restarts. If the UPS detects that the load is greater than 130% in the battery power supply mode, the UPS will beep every 0.5s and display the status on the panel; at the same time, the UPS will switch to bypass mode; this status can only be released by pressing the OFF button.


免费人成再在线观看| 亚洲福利小视频在线观看| 国产天堂网一区二区三区 | 五月天亚洲激情综合av| 午夜国产精品午夜福利网| 国产福利一区二区精品秒拍| 大几吧插进小穴视频| 快速了解国产一级a爱片| 亚洲福利小视频在线观看| 亚洲美女后入在线播放| 97精品人妻人人做人人爽| 久久精品国产自清天天线| 熟妇女人妻丰满中文字幕| 欧美大鸡巴操大骚逼| 美女最骚逼逼视频| 成年人的一级黄色带| 从后面进入嗯啊视频| 国产欧美亚洲一区二区三| 美女大骚逼幸福遍穴| 美女嫩逼插进大屌| 日本老熟妇毛茸茸| 在线看免费无码a片视频| 校花内射国产麻豆欧美一区| 男人操女人黄片黄色| 99久久国产综合精品女| 人人超级碰青青精品| 免看一级a一片成人欧美| 老太太在丛林日老B| 大鸡巴干浪穴视频| 欧美猛男一区二区三区快播| 天堂丝袜人妻中文字幕在线| 国产精品视频一区二区三区分享| 大鸡巴操饿罗斯女人| 欧美精品视频在线| 欧美日韩久久久一区二区三区| 日韩午夜精品中文字幕| 在线12萝自慰喷水| 女生的鸡鸡色色软件| 日本av在线一区二区| 91在线一区二区| 日本精品久久人妻一区二区三区|